Input Description¶
EN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | FALSE | TRUE/FALSE | - |
The input EN has to be driven in edge triggered mode.
The execution of the Function Block is started with a positive edge on the input EN.
In the first call it evaluates its inputs and creates a local copy of them. Afterwards it starts its internal algorithm. It may take several PLC task cycles until it is executed.
Once the execution is completed DONE and its other outputs are set. To start the Function Block again a new positive edge on the input EN has to be applied.
SLOT
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | 0 | 0 … 4 (6) | - |
At input SLOT, the Communication Module slot is specified which should be used by the Function Block.
The internal Communication Module always has the index 0. All external Communication Modules are serially numbered from right to left, starting with 1.
NODE
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
Input NODE specifies the number of the slave. The value 255 sets all slaves to the same time (all slaves are called).
ID
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
Input ID specifies the number of the data record to be read.
DATA
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
DWORD | - | - | - |
Input DATA specifies the first flag of the flag area where the data should be stored.
LEN
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
Input LEN specifies the number of words to be read (has to be even-numbered).