Input Description

MCX_CamSwitchSimple_dc provides the possibility to switch a cam on/off at projected positions. The position is given by an encoder, which must be available, if the cam switch functionality is to be used.

The switch-on-position and the switch-off-position are individually changeable online. Further more a compensation time in both directions can be added to the switch position. Compensation is applied to both switch-on-position and switch-off-position.

../_images/fc4d47dee38a50280a33139000eba54e1

The compensation time makes the switch a “dynamic” switch. The position where to switch on and off is calculated according to the actual velocity, in a way that the output occurs a certain time before (negative compensation) or after (positive compensation) the position has been reached. The time is given at the input compensation, the distance is calculated. The accuracy of time to be reached depends on the stability of velocity, which means just on a constant velocity, the time will be correct.

Distance = velocity * compensation;

The switch will be switched on at “FirstOnPosition + distance” and switched off at “FirstOffPosition + distance”. While switched on, no new calculation of distance will be done.

The actual state of the cam can also be monitored with the output “state”.

../_images/5235591ee38a4fcb0a33139000eba54e1

Enable

Data_Type Default_Value Range Unit
BOOL - - -

The Function Block is activated with Enable TRUE. With Enable=FALSE, the respective cam will be switched off immediately.

FirstOnPosition

Data_Type Default_Value Range Unit
WORD - - -

The value of FirstOnPosition is automatically truncated to the resolution of the circle without notice. For example, all FirstOnPosition greater than 36000 will be limited to 36000 (given if the default resolution of CI51x-ETHCAT cam is used).

FirstOnPosition can be changed at any time. It will be immediately valid after sending to the CI51x-ETHCAT via the POU.

FirstOffPosition

Data_Type Default_Value Range Unit
WORD - - -

The value of FirstOffPosition is automatically truncated to the resolution of the circle without notice. For example, all FirstOffPosition greater than 36000 will be limited to 36000 (given if the default resolution of CI51x-ETHCAT cam is used).

FirstOffPosition can be changed at any time. It will be immediately valid after sending to the CI51x-ETHCAT via the POU.

Note

  • If FirstOnPosition is smaller than FirstOffPosition, the cam is switched on between the values of FirstOnPosition and FirstOffPosition of the same turn. c7894a1ae38a58620a33139000473a6a_6815a9d6e38a53630a33139000eba54e
  • If FirstOnPosition is greater than FirstOffPosition, the cam is switched on between the values of FirstOnPosition of the actual turn and FirstOffPosition of the next turn. c7894a1ae38a58620a33139000473a6a_04d2c890e38a53b10a33139000eba54e
  • If FirstOnPosition is equal to FirstOffPosition, the cam is switched on for one device cycle.

Compensation

Data_Type Default_Value Range Unit
DINT - - µs

The switch action is rescheduled with Compensation:

  • If Compensation is positive, the switch action will be delayed by the value of Compensation.
  • If Compensation is negative, the switch action will be brought forward by the value of Compensation.

CamNumber

Data_Type Default_Value Range Unit
WORD - 1…32 -

Number of the cam: this number runs from 1..32. The parameter cam_To_Track[0..31] must be used to map the cam to the available digital outputs. A configuration tool must be used for setting the cam_To_Track.

csdc

Data type: CSDCX_REF_TYPE

The 2 elements in_csdc and out_csdc of csdc must be initialized with the beginning address of the input data area and the output data area to facilitate proper function of the cam.