ACS_DRIVES_CTRL_STANDARD_GEN Control of ACS Drives with ABB-Drives ProfileΒΆ

../_images/c001af6649c7a2420a331390001b7ced

Function Block ACS_DRIVES_CTRL_STANDARD_GEN is used for controlling ACS Drives with ABB Drives Profile. The Status Word (SW) and Control Word (CW) can be transferred via any generic fieldbus.

Function Block Information

Available as of PLC runtime system: V1.3.2
Included in library: ACSDrivesBase_AC500_V20.lib
Block type Function Block with historical values

Block Description

../_images/a6a585af440b8fb90a331390013d97a9

Function Block ACS_DRIVES_CTRL_STANDARD_GEN is used for controlling ACS Drives with ABB Drives Profile. User has to connect Status Word from the fieldbus to this Function Block input. Function Block generates Control Word, which has to be connected to the fieldbus.

For the necessary configuration of parameters in the drive see table below. Please refer the respective drives manual for parameter setting, if the drive is not mentioned in below table.

Drive Parameter ACS3XX, ACX550 ACS850, ACQ810 ACSM1 ACS580, ACS880 ACS800 Comment
EXT1 COMMANDS 10.01 = COMM 10.01 = FB 10.01 = FBA 20.01 = Fieldbus A 10.01 = COMM.CW Fieldbus interface as source for start and stop
EXT1/EXT2 SEL 11.02 = COMM 12.01 = P.02.22 bit 15 34.01 = P.02.12 bit 15 19.11 = MCW Bit11 (06.01) 11.02 = COMM.CW Fieldbus interface as source to switch to EXT2 control place
REF1 SELECT 11.03 = COMM 21.01 = FBA REF1 24.01 = FBA Ref1 22.11 = FBA ref1 11.03 = COMM.REF Fieldbus interface as source for speed reference
FAULT RESET SEL 16.04 = COMM 10.10 = P.02.22 bit 8 10.08 = P.02.12 bit 8 31.11 = P.06.01 bit 7 16.04 = COMM.CW Fieldbus interface as source for fault reset
PROFILE 53.05 = ABB DRV FULL 51.02 = ABB Drives classic/enhanced 51.02 = ABB Drives classic/enhanced 51.02 = ABB Drives classic/enhanced 98.07 = ABB DRIVES Control Profile to ABB Drives Profile classic or enhanced.