ACS_DRIVES_CTRL_STANDARD_GEN Control of ACS Drives with ABB-Drives ProfileΒΆ
Function Block ACS_DRIVES_CTRL_STANDARD_GEN is used for controlling ACS Drives with ABB Drives Profile. The Status Word (SW) and Control Word (CW) can be transferred via any generic fieldbus.
Function Block Information
Available as of PLC runtime system: | V1.3.2 |
Included in library: | ACSDrivesBase_AC500_V20.lib |
Block type | Function Block with historical values |
Block Description
Function Block ACS_DRIVES_CTRL_STANDARD_GEN is used for controlling ACS Drives with ABB Drives Profile. User has to connect Status Word from the fieldbus to this Function Block input. Function Block generates Control Word, which has to be connected to the fieldbus.
For the necessary configuration of parameters in the drive see table below. Please refer the respective drives manual for parameter setting, if the drive is not mentioned in below table.
Drive Parameter | ACS3XX, ACX550 | ACS850, ACQ810 | ACSM1 | ACS580, ACS880 | ACS800 | Comment |
---|---|---|---|---|---|---|
EXT1 COMMANDS | 10.01 = COMM | 10.01 = FB | 10.01 = FBA | 20.01 = Fieldbus A | 10.01 = COMM.CW | Fieldbus interface as source for start and stop |
EXT1/EXT2 SEL | 11.02 = COMM | 12.01 = P.02.22 bit 15 | 34.01 = P.02.12 bit 15 | 19.11 = MCW Bit11 (06.01) | 11.02 = COMM.CW | Fieldbus interface as source to switch to EXT2 control place |
REF1 SELECT | 11.03 = COMM | 21.01 = FBA REF1 | 24.01 = FBA Ref1 | 22.11 = FBA ref1 | 11.03 = COMM.REF | Fieldbus interface as source for speed reference |
FAULT RESET SEL | 16.04 = COMM | 10.10 = P.02.22 bit 8 | 10.08 = P.02.12 bit 8 | 31.11 = P.06.01 bit 7 | 16.04 = COMM.CW | Fieldbus interface as source for fault reset |
PROFILE | 53.05 = ABB DRV FULL | 51.02 = ABB Drives classic/enhanced | 51.02 = ABB Drives classic/enhanced | 51.02 = ABB Drives classic/enhanced | 98.07 = ABB DRIVES | Control Profile to ABB Drives Profile classic or enhanced. |