BASC_DEVICE¶
Parameter | Value |
---|---|
Library_File_Name | BACnet_B-ASC_AC500_V25.lib |
Firmware | V2.5 |
Type | Type_Function_Block_History |
Group | C interface |
BASC_DEVICE represents the BACnet server device provided by BACnet B-ASC library. The inputs are used to configure corresponding BACnet device object properties. The outputs provide the BACnet device status.
Property | Characteristics | Value | BACnet conformance code |
---|---|---|---|
Object_Identifier | Set via input OBJ_ID | - | R - read |
Object_Name | Set via input OBJ_NAME | - | R - read |
System_Status | Updates output SYS_STATUS | - | R - read |
Object_Type | Constant | DEVICE (8) | R - read |
Vendor_Name | Constant | ABB | R - read |
Vendor_Identifier | Constant | 808 | R - read |
Model_Name | Constant | AC500-PM5xx | R - read |
Firmware_Revision | Constant | B-ASC library V1.0.0 | R - read |
Application_Software_Version | Constant | 0.0.0 | R - read |
Protocol_Version | Constant | 1 | R - read |
Protocol_Revision | Constant | 12 | R - read |
Protocol_Services_Supported | Constant | Who-Is / I-Am Who-Has / I-Have Read property Write property Device communication control |
R - read |
Protocol_Object_Types_Supported | Constant | Analog input Analog output Analog value Binary input Binary output Binary value Device |
R - read |
Object_List | Depends on used objects | - | R - read |
Max_APDU_Length_Accepted | Constant | 480 | R - read |
Segmentation_Supported | Constant | No segmentation (3) | R - read |
APDU_Timeout | Constant | 10000 | R - read |
Number_Of_APDU_Retries | Constant | 0 | R - read |
Device_Address_Binding | Constant | Empty list | R - read |
Database_Revision | Constant | 1 | R - read |
Max_Master | Depends on setting in BASC_SERVER | 127 | R - read |
Max_Info_Frames | Constant | 1 | R - read |