BASC_DEVICE

../_images/782e0b5dabe54b6b0a317d3110ec90af
Parameter Value
Library_File_Name BACnet_B-ASC_AC500_V25.lib
Firmware V2.5
Type Type_Function_Block_History
Group C interface

BASC_DEVICE represents the BACnet server device provided by BACnet B-ASC library. The inputs are used to configure corresponding BACnet device object properties. The outputs provide the BACnet device status.

Device object properties provided at the BACnet network by BASC_DEVICE
Property Characteristics Value BACnet conformance code
Object_Identifier Set via input OBJ_ID - R - read
Object_Name Set via input OBJ_NAME - R - read
System_Status Updates output SYS_STATUS - R - read
Object_Type Constant DEVICE (8) R - read
Vendor_Name Constant ABB R - read
Vendor_Identifier Constant 808 R - read
Model_Name Constant AC500-PM5xx R - read
Firmware_Revision Constant B-ASC library V1.0.0 R - read
Application_Software_Version Constant 0.0.0 R - read
Protocol_Version Constant 1 R - read
Protocol_Revision Constant 12 R - read
Protocol_Services_Supported Constant

Who-Is / I-Am

Who-Has / I-Have

Read property

Write property

Device communication control

R - read
Protocol_Object_Types_Supported Constant

Analog input

Analog output

Analog value

Binary input

Binary output

Binary value

Device

R - read
Object_List Depends on used objects - R - read
Max_APDU_Length_Accepted Constant 480 R - read
Segmentation_Supported Constant No segmentation (3) R - read
APDU_Timeout Constant 10000 R - read
Number_Of_APDU_Retries Constant 0 R - read
Device_Address_Binding Constant Empty list R - read
Database_Revision Constant 1 R - read
Max_Master Depends on setting in BASC_SERVER 127 R - read
Max_Info_Frames Constant 1 R - read