BASC_DEVICE¶
| Parameter | Value |
|---|---|
| Library_File_Name | BACnet_B-ASC_AC500_V25.lib |
| Firmware | V2.5 |
| Type | Type_Function_Block_History |
| Group | C interface |
BASC_DEVICE represents the BACnet server device provided by BACnet B-ASC library. The inputs are used to configure corresponding BACnet device object properties. The outputs provide the BACnet device status.
| Property | Characteristics | Value | BACnet conformance code |
|---|---|---|---|
| Object_Identifier | Set via input OBJ_ID | - | R - read |
| Object_Name | Set via input OBJ_NAME | - | R - read |
| System_Status | Updates output SYS_STATUS | - | R - read |
| Object_Type | Constant | DEVICE (8) | R - read |
| Vendor_Name | Constant | ABB | R - read |
| Vendor_Identifier | Constant | 808 | R - read |
| Model_Name | Constant | AC500-PM5xx | R - read |
| Firmware_Revision | Constant | B-ASC library V1.0.0 | R - read |
| Application_Software_Version | Constant | 0.0.0 | R - read |
| Protocol_Version | Constant | 1 | R - read |
| Protocol_Revision | Constant | 12 | R - read |
| Protocol_Services_Supported | Constant | Who-Is / I-Am Who-Has / I-Have Read property Write property Device communication control |
R - read |
| Protocol_Object_Types_Supported | Constant | Analog input Analog output Analog value Binary input Binary output Binary value Device |
R - read |
| Object_List | Depends on used objects | - | R - read |
| Max_APDU_Length_Accepted | Constant | 480 | R - read |
| Segmentation_Supported | Constant | No segmentation (3) | R - read |
| APDU_Timeout | Constant | 10000 | R - read |
| Number_Of_APDU_Retries | Constant | 0 | R - read |
| Device_Address_Binding | Constant | Empty list | R - read |
| Database_Revision | Constant | 1 | R - read |
| Max_Master | Depends on setting in BASC_SERVER | 127 | R - read |
| Max_Info_Frames | Constant | 1 | R - read |