Access R/W

EN

Way of Access: Toggle

Description: EN input

Enables the Function Block by TRUE value of input EN.

SLOT

Way of Access: Text

Description: SLOT, in which CM572-DP is mounted.

DEV_NAME (device name)

Data type: STRING, Default value: “Not Available”, Range: 1 to 240

At input DEV_NAME, the name of the drive (slave) from which the parameter value to be read must be specified.

The Function Block is designed to be used with a fix SLAVE device.

If the DEV_NAME is given incorrect or invalid, then the Function Block will displays an error. In such case ERR=TRUE and ERNO=16#4030.

Note

The DEV_NAME input should not be changed, while the program is running. If changed, nevertheless the new value will become effective only after the Function Block is enabled again.

DRIVE_TYPE

Way of Access: Text

Description: DRIVE_TYPE input

NVAR

Way of Access: Text

Description: Number of drive parameters to be read from drive using PROFIBUS.