PNIO_READ_EXTΒΆ

../_images/8a694931e38ae48a0a33139000eba54e
Parameter Value
Library_File_Name PROFINET_AC500_V13.lib
Firmware V2.2.0
Type Type_Function_Block_History
Group Data

The Function Block PNIO_READ_EXT implements the acyclic PROFINET READ service. Using this function, the controller has read access to API, slot, sub slot and index-related data of PROFINET IO Devices. PNIO_READ_EXT works outside the cyclic process data exchange.

Every time a FALSE->TRUE edge is applied to input EN, PNIO_READ_EXT reads the data at its inputs and sends a corresponding request message to the Communication Module. Further FALSE->TRUE edges at input EN are ignored until the processing of the active requests is finished. The completion of the request processing is indicated by DONE = TRUE.