PNIO_READ_EXTΒΆ
Parameter | Value |
---|---|
Library_File_Name | PROFINET_AC500_V13.lib |
Firmware | V2.2.0 |
Type | Type_Function_Block_History |
Group | Data |
The Function Block PNIO_READ_EXT implements the acyclic PROFINET READ service. Using this function, the controller has read access to API, slot, sub slot and index-related data of PROFINET IO Devices. PNIO_READ_EXT works outside the cyclic process data exchange.
Every time a FALSE->TRUE edge is applied to input EN, PNIO_READ_EXT reads the data at its inputs and sends a corresponding request message to the Communication Module. Further FALSE->TRUE edges at input EN are ignored until the processing of the active requests is finished. The completion of the request processing is indicated by DONE = TRUE.