PROFINET Scan and Compare View

PNIO_Controller

  1. After going online, double-click on PNIO_Controller (PROFINET-IO-Controller) in the device tree.

    The editor PNIO_Controller will be displayed.

  2. Select tab Diagnostics live list and click Scan to find all hardware devices that exist.

    The found devices will be listed in a table.

  3. Click Compare to compare the found hardware I/O devices with the current project configuration.

Unknown hardware

In the case, that any I/O hardware device is unknown:

  • The devices will be marked with a red exclamation,
  • A message box will be appear for each unknown device
  • Automation_Builder generate one message with information about its vendor ID and device ID
../_images/2fdb4d75caaef3690a317f343a9e6923
../_images/5653ac21caaef51e0a317f34435291d0

Diff-View

  1. In order to display the compare Diff-View, install the device description for the unknown device.

  2. After installing the device description, click Scan again and click Compare.

    ../_images/a291895dcaaef6b30a317f342f021fc5

    The message box informs you, that the application will go offline to display the compare-view.

  3. Click Yes

    The Project Comparison - Differences tab displays the difference between the PROFINET configuration in Automation_Builder (left side) and the real hardware configuration (right side).

    ../_images/b394c69fcaaef7ad0a317f345e3703b2
  4. Click Accept Single to accept only a part of the differences or Accept Block to accept all differences.

    After clicking on the Button Accept Single or Accept Block the found devices will be moved from the right side to the left side

  5. Close tab Project Comparison - Differences

    A message will be displayed to ask if you want to commit the new changes into project or not:

    ../_images/72a3b5e3caaeff5b0a317f341b6a1db8
  6. Click Yes

    the changes will be saved and the devices will be added to the project.

    ../_images/b1ebca81caaf69240a317f347f589fa5