1000hex…1FFFhex - Device Error¶
DEC | HEX | Error description |
---|---|---|
4097 | 1001 | Device does not exist |
4098 | 1002 | Command not supported by the device. The function is not supported by the device firmware/hardware. Block library newer than the device firmware. FC..: No high-speed counter available at the given module. |
4100 | 1004 | Error operating mode. FC..: Operating mode “0” -> No counter set in the PLC configuration. |
4101 | 1005 | Invalid status FLASH_READ: Block is not written yet FLASH_WRITE: Block was already written RETAIN..: No program loaded Library PROFINET IO: PNIO_WRITE, PNIO_READ: Internal error. Restart the PLC. |
4117 | 1015 | Format error SD..: File cannot be read because of an invalid format. Data could not be read or not be read completely. |
4119 | 1017 | Incorrect length PERSISTENT..: Data have an incorrect length RETAIN..: Data have an incorrect length |
4120 | 1018 | Checksum error |
4122 | 101A | FC..: Internal error (e.g. no CS31 Adr parameter found, wrong size of CS31 Adr) HA..: Internal error (e.g. null pointer received, wrong return value of internal function, no entry in configuration found) |
4123 | 101B | Device access error Flash..: Resources are not available HA..: Remote CPU failure: Other CPU is off or out of order PERSISTENT..: Data could not be copied, access error or no data do exist RETAIN..: Data could not be copied, access error or no data do exist SD..: Access to the SD card is not possible (e.g. memory exhausted, file already opened, etc. |
4124 | 101C | Incorrect number PERSISTENT..: Because of the current CPU parameters, data are loaded only partly |
4127 | 101F | Access protection SD..: SD card is write protected |
4128 | 1020 | Error when opening SD..: Error when opening a file stored on the SD card |
4129 | 1021 | Not found FC..: CS31 Bus Module not found ETHERCAT Modul not found HA_CS31_CONTROL: Own CI590-CS31-HA slave failure (missing module) HA_CS31_DIAG: One or more CI590-CS31-HA slave(s) is/are inactive HA_CS31_DIAG_VIA_CM574-RS: One or more CI590 are inactive SD..: The searched sector could not be found in the file TASK_INFO: Unknown task |
4130 | 1022 | End reached SD..: Section end or end of file reached PERSISTENT..: Because of the current CPU parameters, data are not loaded |
4131 | 1023 | Reading error FLASH..: Reading error in data segment: Incorrect checksum |
4132 | 1024 | Writing error FLASH..: Block cannot be programmed SD..: File could not be deleted or written |
4137 | 1029 | FC..: Wrong configuration (e.g. no CM574-RS configured on specified slot) HA..: Remote CI590-CS31-HA slave failure (missing module) |
8191 | 1FFF | Not ready Flash..: The command is already executed by an other instance SD..: Command cannot be executed. Another instance is already active. |