Global State Field

../_images/22ab63d046008d240a33139000eba54e1
Parameter Description
Global state bits The Global state bits are described in detail in section Master Status.
Master main state A description about the task Master main state you find in section Master Operation Mode.
Error remote address Displays the lowest station address, which signals diagnosis. Further information about this you find in Station Status.
Error event Indicates the occurred error of the Error remote address. Further information about this you find in Station Status.
Bus error counter The Bus error counter is increased, whenever an increased number of faulty CAN frames were detected. For further information see section Bus Monitoring.
Bus off counter This counter counts the number of reported bus-off-events. For further information see Bus Monitoring.
Timeout counter Number of aborted transmission of CAN message. The messages are lost. It is an indication that no other CAN device was connected or responsive at this time to acknowledge the sent message requests. Bus Diagnosis.
Receive Overflow This counter is incremented, if the master is in overrun because of too many received messages. If this counter is unequal 0, the loss of CAN messages can be assumed. Normally this counter should be 0.
Node 7-0 param. 8 Bit parameter state Node 0-7
Node 15-8 param. 8 Bit parameter state Node 8-15
Node 126-120 param. 8 Bit parameter state Node 56-63
Node 7-0 active 8 Bit active state Node 0-7
Node 15-8 active 8 Bit active state Node 8-15
Node 126-120 active 8 Bit active state Node 56-63
Node 7-0 diagnostic 8 8 Bit diagnostic state Node 0-7
Node 15-8 diagnostic 8 Bit diagnostic state Node 8-15
Node 126-120 diagnostic 8 Bit diagnostic state Node 56-63