Variables Configuration - VAR_CONFIG¶
Use the variables configuration for mapping variables of functions blocks to the process map. For declarations in the function block, assign the variables to the device inputs/outputs without providing the full address. Later, the exact address is provided centrally for all function block instances of the application in a global variable list including VAR_CONFIG
declarations. This global variables list with the VAR_CONFIG
declarations is termed the “variables configuration”.
Attention
For changes to variables that are assigned to I/O addresses, CODESYS displays them immediately In the process map. For changes to variables that are mapped by a variables configuration, CODESYS displays them not until the end of the responsible task.
Declaration of variables in functions blocks
When declaring variables in a function block, declare the variables between the keywords VAR
and END_VAR
and assign incomplete addresses to the variables. Mark these incomplete addresses with an asterisk (\*
).
Syntax:
<identifier> AT %<I\\\|Q>\*:<data type>;
Example
Define two local I/O variables: the input variable xLocIn
and the output variable xLocOut
.
FUNCTION_BLOCK locio
VAR
xLocIn AT %I*: BOOL := TRUE;
xLocOut AT %Q*: BOOL;
END_VAR
Final definition of addresses in the variables configuration of the global variables list
In the global variables list that you use as the variables configuration, define the variable declarations with the absolute addresses between the keywords VAR_CONFIG
and END_VAR
.
You must declare the VAR_CONFIG
variables with the complete instance path, separating the individual POU and instance name by a dot (.). The declaration must include an address whose class (input/output) agrees with the class of the incomplete address (%I*, %Q*) in the function block. The data type must also agree.
Syntax:
<instance variable path> AT %<I\\\|Q><location>: <data type>;
If the path instance does not exist, then an error is reported. CODESYS prints an error also if there is not an address configuration available for a variable that you declared with an incomplete address.
Example
The locio
function block in the example above is used in a program as follows:
PROGRAM PLC_PRG
VAR
locioVar1: locio;
locioVar2: locio;
END_VAR
A correct variables configuration in a global variable list could then look like this:
VAR_CONFIG
PLC_PRG.locioVar1.xLocIn AT %IX1.0 : BOOL;
PLC_PRG.locioVar1.xLocOut AT %QX0.0 : BOOL;
PLC_PRG.locioVar2.xLocIn AT %IX1.0 : BOOL;
PLC_PRG.locioVar2.xLocOut AT %QX0.3 : BOOL;
END_VAR
See also
Creating a variables configuration
Requirement: You have a project open that includes a controller configuration with a field device. The project contains a program (e.g. PLC_PRG
) and a function block (e.g. func1
). The field device has inputs and outputs. The textual view is selected in the options for the declaration editor.
Double-click a function block in the device tree (e.g.
func1
).- ⇒
The function block editor opens.
Type the following between the keywords
VAR
andEND_VAR
:xLocIn AT %I\*: BOOL := TRUE;
andXLocOut AT %Q\*:BOOL;
in the next line.- ⇒
You have declared an input variable
xLocIn
and assigned it to the incomplete input address%I\*
of a field device. You have assigned the declared output variables have to the incomplete output address%Q\*
.
Click the
PLC_PRG
object in the device tree and add the following to the declaration section of the program betweenVAR
andEND_VAR
:locioVar1: func;
locioVar2: func;
Right-click the Application object in the device tree and click and then click Add in the Add Global Variable List dialog box.
- ⇒
The global variables list is added to the device tree and opens in the editor.
Change the keyword
VAR_GLOBAL
toVAR_CONFIG
.Click
.- ⇒
The following instance paths are added:
PLC_PRG.logioVar1.xLocIn AT %I\*;
PLC_PRG.logioVar2.xLocIn AT %I\*;
PLC_PRG.logioVar1.xLocOut AT %Q\*;
PLC_PRG.logioVar2.xLocOut AT %Q\*;
Now, replace the incomplete addresses
%I\*
and%Q\*
with the absolute, complete addresses.