DigiVis500 configurationΒΆ
Digivis500 Version 1.0SP2 US
The DigiVis500 does not work with the local IP 127.0.0.1.
OPC-S shows an error Invalid computer name.
PC configuration with a fixed IP 192.168.9.253 is possible.
With DigiVis500 installation the ABB OPC Tunnel is installed and registered automatically as service (session 0) with Startup type: Automatic. Automatic means ABB OPC Tunnel will start as soon as the Windows system starts up.
With the start of the ABB OPC Tunnel (OCTsvc.exe), the OPCServer (WinCoDeSysOPC.exe) and also the IEC 61131-3 editor gateway server (Gateway.exe) are started in session 0.
PC configuration with a fixed IP 192.168.9.253 is possible.
After loading of the Graphics Builder configuration into the Operation, the Operation is running with actual OPC values.
All relevant processes
- OPC Tunnel
- Gateway.exe
- WinCoDeSysOPC.exe
are running in the same session.