Technical Data of the Digital \ Outputs¶
Parameter | Value |
---|---|
Number of channels per module | 8 |
Distribution of the channels into groups | 1 group of 8 channels |
Terminals of the channels DO0 to DO7 | Terminals 4.0 to 4.7 |
Reference potential for all outputs | Terminals 2.9 … 4.9 (negative pole of the supply voltage, signal name ZP) |
Common power supply voltage | For all outputs terminal 4.8 (positive pole of the supply voltage, signal name UP3) |
Output voltage for signal 1 | UP3 (-0.8 V) |
Output delay (0->1 or 1->0) | On request |
Output current | |
Rated value per channel | 500 mA at UP3 = 24 V |
Max. value (all channels together) | 4 A |
Leakage current with signal 0 | < 0.5 mA |
Fuse for UP3 | 10 A fast |
Demagnetization with inductive DC load | Via internal varistors (see figure below this table) |
Output switching frequency | |
With resistive load | On request |
With inductive loads | Max. 0.5 Hz |
With lamp loads | 11 Hz max. at 5 W max. |
Short-circuit-proof / overload-proof | Yes |
Overload message (I > 0.7 A) | Yes, after ca. 100 ms |
Output current limitation | Yes, automatic reactivation after short circuit/overload |
Resistance to feedback against 24 V signals | Yes (software-controlled supervision) |
Max. cable length | |
Shielded | 1000 m |
Unshielded | 600 m |
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.
Digital input/output (circuit diagram)
1 | Digital output |
2 | Varistors for demagnetization when inductive loads are turned off |