Technical Data of the Analog Inputs

Parameter Value
Number of channels per module 4
Distribution of channels into groups 1 group with 4 channels
Connection if channels AI0+ to AI3+ Terminals 2.0 to2.3
Reference potential for AI0+ to AI3+

Terminal 2.4 (AI-) for voltage and RTD measurement

Terminal 2.9, 3.9 and 4.9 for current measurement

Input type  
  Unipolar Voltage 0…10 V, current or Pt100/Pt1000/Ni1000
  Bipolar Voltage -10…+10 V
Galvanic isolation Against CANOPEN Bus
Configurability 0…10 V, -10…+10 V, 0/4…20 mA, Pt100/1000, Ni1000 (each input can be configured individually)
Channel input resistance

Voltage: > 100 kW

Current: ca. 330 W

Time constant of the input filter

Voltage: 100 µs

Current: 100 µs

Indication of the input signals 1 LED per channel (brightness depends on the value of the analog signal)
Conversion cycle 1 ms (for 4 inputs + 2 outputs); with RTDs Pt/Ni… 1 s
Resolution

Range 0…10 V: 12 bits

Range -10…+10 V: 12 bits + sign

Range 0…20 mA: 12 bits

Range 4…20 mA: 12 bits

Range RTD (Pt100, PT1000, Ni1000): 0.1 °C

Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ. 0.5 %, max. 1 %
Relationship between input signal and hex code Tables Input Ranges Voltage, Current CI581-CN and Digital Input and Input Range Resistor CI581-CN
Unused inputs Are configured as “unused” (default value)
Overvoltage protection Yes