TK506 - RS-485 Isolator for COM1

  • Isolated side: 5-pin terminal
  • AC500-eCo-side: D-sub 9, male
  • Length 0.6 m
../_images/6009ff2ee38796ca0a33139000eba54e

Intended Purpose

The RS485 Isolator TK506 for COM1 of processor modules PM55x and PM56x allows longer cable length for serial communication. The product can be used for the communication protocols MODBUS RTU or CS31 System Bus.

Note

The RS-485 isolator TK506 supports the processor modules PM55x and PM56x with the following ordering nos. and version indexes:

  • Ordering nos. 1TNE968900Rxxxx with version index ≥ A3 (see image below)
  • Ordering nos. 1SAP12xx00Rxxxx independent of the version index <no title>
../_images/5b302daa41a77a2e0a317f343481d5b9

The isolator provides galvanic isolation of the RS-485 communication signals. It is supplied via the 3.3 V output of the COM1 interface of the Processor Module. The isolator automatically detects and follows serial data flow direction changes. It is adapted to communication speeds up to 187.5 kBaud.

Connection: Interface

../_images/4dfff12be387966c0a33139000eba54e
Pin No. Signal Description
1 Terminator P Terminator positive
2 RxD/TxD-P Receive/transmit positive
3 RxD/TxD-N Receive/transmit negative
4 Terminator N Terminator negative
5 FE Functional earth (internally connected to DIN rail spring)

RS-485 communication requires an electrical termination of the communication line. The following is necessary:

  • 2 resistors of 120 W each at both line ends (to avoid signal reflections)
  • a pull-up resistor at RxD/TxD-P and a pull-down resistor at RxD/TxD-N. These 2 resistors care for a defined high level on the bus, while there is no data exchange.

In every RS-485 network 1 pull-up and pull-down resistors must be activated. It is recommended to activate the pull-up and the pull-down resistors at the bus master. These 2 resistors are integrated inside the TK506 RS-485 isolator. They can be activated by connecting the terminals 1-2 and 3-4 of the terminal block with cable bridges.

Connection: MODBUS Protocol

The following figure shows an RS-485 bus with the bus master at the line end.

../_images/f4d4844be38788a70a33139000eba54e

If the master is located within the bus line, it does not need a terminating resistor. The pull-up and the pull-down resistors, however, are necessary:

../_images/bb7677b2e38788f50a33139000eba54e

Attention

:strong:Risk of EMC disturbances!

Unshielded cables may cause EMC disturbances.

Always use shielded cables and connect the shield at every device.

Attention

:strong:Risk of malfunctions!

The pull-up resistors must be used only one time within a bus line.

Use the pull-up resistors only at 1 master.

The cable shields must be grounded CS31 bus.

Connection: CS31 Protocol

The following figure shows an CS31 Bus with the bus master at the line end.

../_images/b7d41d2142d6c4a40a33139063a65799

If the master is located within the bus line, it does not need a terminating resistor. The pull-up and the pull-down resistors, however, are necessary:

../_images/ec9479f842da59d10a33139058fca0a9

Attention

:strong:Risk of EMC disturbances!

Unshielded cables may cause EMC disturbances.

Always use shielded cables and connect the shield at every device.

Technical Data

Physical link RS-485
Electrical Isolation Yes
Usage / Supported protocols

MODBUS (Master and Slave)

CS31 (Master only)

Supported baudrates [baud]  
  MODBUS 9.6 k, 14.4 k, 19.2 k, 38.4 k and 187.5 k
  CS31 system bus 187.5 k
Connector at the communication line 5-pin screw terminal block
Connector at PM554 or PM564 D-sub 9, male
Cable type and specification

Twisting rate minimum 10 per meter, with common shield

Capacitance between the cores: < 55 nF/km

Characteristic impedance: 120 W

  Recommended cable cross section

Conductor cross section 0.5 mm²

Resistance per core: < 40 W/km

  Thinnest cable cross section

Conductor cross section 0.22 mm²

Resistance per core: < 100 W/km

Max. cable length for MODBUS  
  at 38.4 kBaud or below 1200 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm²
  at 187.5 kBaud 500 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm²
Max. cable length for CS31 system bus 500 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm²
Specification for external termination resistor 120 W, 1 %, 0.25 W
Length 0.6 m
Weight 80 g
Isolation voltage 500 VDC (type test)
Surge voltage (common mode) 1000 V (type test)

Ordering Data

Order No. Scope of delivery Product life cycle status
1SAP 186 100 R0001 TK506, RS-485 isolator D-sub 5 terminal Active

Note

*) For planning and commissioning of new installations use modules in Active status only.