TK506 - RS-485 Isolator for COM1¶
- Isolated side: 5-pin terminal
- AC500-eCo-side: D-sub 9, male
- Length 0.6 m
Intended Purpose
The RS485 Isolator TK506 for COM1 of processor modules PM55x and PM56x allows longer cable length for serial communication. The product can be used for the communication protocols MODBUS RTU or CS31 System Bus.
Note
The RS-485 isolator TK506 supports the processor modules PM55x and PM56x with the following ordering nos. and version indexes:
- Ordering nos. 1TNE968900Rxxxx with version index ≥ A3 (see image below)
- Ordering nos. 1SAP12xx00Rxxxx independent of the version index <no title>
The isolator provides galvanic isolation of the RS-485 communication signals. It is supplied via the 3.3 V output of the COM1 interface of the Processor Module. The isolator automatically detects and follows serial data flow direction changes. It is adapted to communication speeds up to 187.5 kBaud.
Connection: Interface
Pin No. | Signal | Description |
---|---|---|
1 | Terminator P | Terminator positive |
2 | RxD/TxD-P | Receive/transmit positive |
3 | RxD/TxD-N | Receive/transmit negative |
4 | Terminator N | Terminator negative |
5 | FE | Functional earth (internally connected to DIN rail spring) |
RS-485 communication requires an electrical termination of the communication line. The following is necessary:
- 2 resistors of 120 W each at both line ends (to avoid signal reflections)
- a pull-up resistor at RxD/TxD-P and a pull-down resistor at RxD/TxD-N. These 2 resistors care for a defined high level on the bus, while there is no data exchange.
In every RS-485 network 1 pull-up and pull-down resistors must be activated. It is recommended to activate the pull-up and the pull-down resistors at the bus master. These 2 resistors are integrated inside the TK506 RS-485 isolator. They can be activated by connecting the terminals 1-2 and 3-4 of the terminal block with cable bridges.
Connection: MODBUS Protocol
The following figure shows an RS-485 bus with the bus master at the line end.
If the master is located within the bus line, it does not need a terminating resistor. The pull-up and the pull-down resistors, however, are necessary:
Attention
:strong:Risk of EMC disturbances!
Unshielded cables may cause EMC disturbances.
Always use shielded cables and connect the shield at every device.
Attention
:strong:Risk of malfunctions!
The pull-up resistors must be used only one time within a bus line.
Use the pull-up resistors only at 1 master.
The cable shields must be grounded CS31 bus.
Connection: CS31 Protocol
The following figure shows an CS31 Bus with the bus master at the line end.
If the master is located within the bus line, it does not need a terminating resistor. The pull-up and the pull-down resistors, however, are necessary:
Attention
:strong:Risk of EMC disturbances!
Unshielded cables may cause EMC disturbances.
Always use shielded cables and connect the shield at every device.
Technical Data
Physical link | RS-485 | |
Electrical Isolation | Yes | |
Usage / Supported protocols | MODBUS (Master and Slave) CS31 (Master only) |
|
Supported baudrates [baud] | ||
MODBUS | 9.6 k, 14.4 k, 19.2 k, 38.4 k and 187.5 k | |
CS31 system bus | 187.5 k | |
Connector at the communication line | 5-pin screw terminal block | |
Connector at PM554 or PM564 | D-sub 9, male | |
Cable type and specification | Twisting rate minimum 10 per meter, with common shield Capacitance between the cores: < 55 nF/km Characteristic impedance: 120 W |
|
Recommended cable cross section | Conductor cross section 0.5 mm² Resistance per core: < 40 W/km |
|
Thinnest cable cross section | Conductor cross section 0.22 mm² Resistance per core: < 100 W/km |
|
Max. cable length for MODBUS | ||
at 38.4 kBaud or below | 1200 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm² | |
at 187.5 kBaud | 500 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm² | |
Max. cable length for CS31 system bus | 500 m with cable cross section 0.5 mm² or 400 m with cable cross section 0.22 mm² | |
Specification for external termination resistor | 120 W, 1 %, 0.25 W | |
Length | 0.6 m | |
Weight | 80 g | |
Isolation voltage | 500 VDC (type test) | |
Surge voltage (common mode) | 1000 V (type test) |
Ordering Data
Order No. | Scope of delivery | Product life cycle status |
---|---|---|
1SAP 186 100 R0001 | TK506, RS-485 isolator D-sub 5 terminal | Active |
Note
*) For planning and commissioning of new installations use modules in Active status only.