LED State DisplaysΒΆ
The PROFIBUS state is shown by state LEDs.
LED | Color | Status | Description |
---|---|---|---|
PWR | green | ON (light) | Power supply available. |
OFF (dark) | Power supply not available or defective hardware. | ||
RDY | yellow | ON | Boot procedure |
Blinking | Boot failure | ||
OFF | β | ||
RUN | green | ON | Communication module is operational |
Blinking | β | ||
OFF | Communication module is not operational | ||
STA | green | ON | Communication to all slaves is established |
Flashes cyclic | β | ||
Flashes non-cyclic | No configuration or stack error | ||
OFF | No communication | ||
ERR | red | ON | Communication to one/all slaves is disconnected |
Flashes cyclic | Communication to at least one slave is disaconnected | ||
OFF | No error |