Connection of resistance thermometers in 3-wire configuration to the \ analog inputs¶
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow through them to build the necessary voltage drop for the evaluation. For this, the module DA502 provides a constant current source which is multiplexed over max. 4 analog input channels.
The following figure shows the connection of resistance thermometers in 3-wire configuration to the analog inputs AI0 and AI1. Proceed with the analog inputs AI2 and AI3 in the same way.
Connection of resistance thermometers in 3-wire configuration to the analog inputs
With 3-wire configuration, 2 adjacent analog channels belong together (e. g. the channels 0 and 1). In this case, both channels are configured according to the desired operating mode. The lower address must be the even address (channel 0), the next higher address must be the odd address (channel 1).
The constant current of one channel flows through the resistance thermometer. The constant current of the other channel flows through one of the cores. The module calculates the measured value from the two voltage drops and stores it under the input with the higher channel number (e. g. I1).
In order to keep measuring errors as small as possible, it is necessary to have all the involved conductors in the same cable. All the conductors must have the same cross section.
The following measuring ranges can be configured DA502 - Digital/Analog Input/Output Module DA502 - Digital/Analog Input/Output Module:
Pt100 | -50 °C…+400 °C | 3-wire configuration, 2 channels used |
Pt1000 | -50 °C…+400 °C | 3-wire configuration, 2 channels used |
Ni1000 | -50 °C…+150 °C | 3-wire configuration, 2 channels used |
For a description of the function of the LEDs, please refer to Diagnosis and displays / Displays DA502 - Digital/Analog Input/Output Module.
The module DA502 performs a linearization of the resistance characteristic.
To avoid error messages from unused analog input channels, configure them as “unused”.