Electrical Connection

The digital/analog input/output module DA502 can be connected to the following devices via the I/O bus connector:

  • CS31 bus modules, e. g. DC551-CS31, CI590 and CI592
  • AC500 CPUs (PM5xx)
  • other AC500 I/O devices

Note

The DA502 must not be used as a decentralized communication interface module at DC505-FBP.

Note

For a detailed description of the mounting, disassembly and electrical connection of the module, please refer to the System Assembly, Construction and Connection chapter AC500 (Standard).

The electrical connection is carried out by using the 40 terminals of the terminal unit TU515/TU516 TU515, TU516, TU516-H and TU542 for I/O Modules.

The assignment of the terminals:

Terminal Signal Description
1.0 DO0 Signal of the digital output DO0
1.1 DO1 Signal of the digital output DO1
1.2 DO2 Signal of the digital output DO2
1.3 DO3 Signal of the digital output DO3
1.4 DO4 Signal of the digital output DO4
1.5 DO5 Signal of the digital output DO5
1.6 DO6 Signal of the digital output DO6
1.7 DO7 Signal of the digital output DO7
1.8 UP Process voltage UP (24 VDC)
1.9 ZP Process voltage ZP (0 VDC)
2.0 DO8 Signal of the digital output DO8
2.1 DO9 Signal of the digital output DO9
2.2 DO10 Signal of the digital output DO10
2.3 DO11 Signal of the digital output DO11
2.4 DO12 Signal of the digital output DO12
2.5 DO13 Signal of the digital output DO13
2.6 DO14 Signal of the digital output DO14
2.7 DO15 Signal of the digital output DO15
2.8 UP Process voltage UP (24 VDC)
2.9 ZP Process voltage ZP (0 VDC)
3.0 AI0+ Positive pole of analog input signal 0
3.1 AI1+ Positive pole of analog input signal 1
3.2 AI2+ Positive pole of analog input signal 2
3.3 AI3+ Positive pole of analog input signal 3
3.4 AI- Negative pole of analog input signals 0 to 3
3.5 AO0+ Positive pole of analog output signal 0
3.6 AO1+ Positive pole of analog output signal 1
3.7 AO- Negative pole of analog output signals 0 and 1
3.8 UP Process voltage UP (24 VDC)
3.9 ZP Process voltage ZP (0 VDC)
4.0 DC16 Signal of the configurable digital input/output DC16
4.1 DC17 Signal of the configurable digital input/output DC17
4.2 DC18 Signal of the configurable digital input/output DC18
4.3 DC19 Signal of the configurable digital input/output DC19
4.4 DC20 Signal of the configurable digital input/output DC20
4.5 DC21 Signal of the configurable digital input/output DC21
4.6 DC22 Signal of the configurable digital input/output DC22
4.7 DC23 Signal of the configurable digital input/output DC23
4.8 UP Process voltage UP (24 VDC)
4.9 ZP Process voltage ZP (0 VDC)

The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at the terminals L+/UP and M/ZP of the CPU/Bus Module increases by 2 mA per DA502.

The external power supply connection is carried out via the UP (+24 VDC) and the ZP (0 VDC) terminals.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

Attention

:strong:Risk of damaging the PLC modules!

The PLC modules must not be removed while the plant is connected to a power supply.

Make sure that all voltage sources (supply and process voltage) are switched off before you

  • connect or disconnect any signal or terminal block
  • remove or replace a module.

Caution

:strong:Risk of imprecise and faulty measurements!

Analog signals may be distorted seriously by external electromagnetic influences.

Use shielded wires when wiring analog signal sources. The cable shield must be grounded at both ends of the cable. Provide a potential equalization of a low resistance to avoid high potential differences between different parts of the plant.

../_images/276a222d8ff0db660a3313906389dd7d

Terminal assignment of the module

The module provides several diagnosis functions DA502 - Digital/Analog Input/Output Module.