Number of channels per module |
8 outputs (with transistors, non-latching type) |
Distribution of the channels into groups |
2 groups of 4 channels |
Connection of the channels |
|
|
O0 to O3 |
Terminals 3.0, 3.1, 3.4, 3.5 |
|
O4 to O7 |
Terminals 4.0, 4.1, 4.4, 4.5 |
Indication of the output signals |
1 yellow LED per channel, the LED is ON if the output signal is high (signal 1) |
Power supply voltage for the module |
Terminals 1.8 and 2.8 (positive pole of the process supply voltage, signal name UP) |
Reference potential for module power supply |
Terminals 1.9 and 2.9 (negative pole of the process supply voltage, signal name ZP) |
Power supply voltage for the outputs O0 to O3 |
Terminal 3.8 (positive pole of the process supply voltage, signal name UP3) |
Reference potential for the outputs O0 to O3 |
Terminal 3.9 (negative pole of the process supply voltage, signal name ZP3) |
Power supply voltage for the outputs O4 to O7 |
Terminal 4.8 (positive pole of the process supply voltage, signal name UP4) |
Reference potential for the outputs O4 to O7 |
Terminal 4.9 (negative pole of the process supply voltage, signal name ZP4) |
Output voltage for signal 1 |
UP (-0.4 V) |
Output delay (0->1 or 1->0) |
On request |
Output current |
|
|
Rated value, per channel |
2 A at UP3 or UP4 = 24 V |
|
Maximum value (channels O0 to O3) |
8 A |
|
Maximum value (channels O4 to O7) |
8 A |
Leakage current with signal 0 |
< 0.1 mA |
Rated protection fuse on UP |
10 A fast |
Demagnetization when inductive loads are switched off |
With clamp diode in output high side driver |
Switching frequency |
|
|
With resistive load |
On request |
|
With inductive loads |
Max. 2 Hz |
|
With lamp loads |
Max. 11 Hz with max. 48 W |
Short-circuit proof / overload proof |
No (should be done externally) |
Overload message |
No |
Output current limitation |
No (should be done externally) |
Resistance to feedback against 24V signals |
Yes to UP3 or UP4. No to outputs in same group. |
Max. cable length |
|
|
Shielded |
1000 m |
|
Unshielded |
600 m |