Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Process supply voltage UP, UP3 and UP4  
  Connections

Terminals 1.8 and 2.8 for +24 V (UP) as well as 1.9 and 2.9 0 V (ZP)

Terminals 3.8 for +24 V (UP3) as well as 3.9 for 0 V (ZP3)

Terminals 4.8 for +24 V (UP4) as well as 4.9 for 0 V (ZP4)

  Rated value 24 VDC
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse on UP, UP3 and UP4 10 A fast (for each process supply voltage)
  Galvanic isolation Yes, per module and per output channel groups
Current consumption  
  From 24 VDC power supply at the terminals UP/L+ and ZP/M of the CPU/bus module Ca. 2 mA
  From UP at normal operation / with outputs Ca. 20 mA + 1.5 mA per output
  From UP3 or UP4 at normal operation / with outputs Ca. 0.01 A + max. 2 A per output
  Inrush current from UP (at power up) 0.015 A²s
  Inrush current from UP3 or UP4 (at power up) 0.005 A²s (without output load)
Max. power dissipation within the module 6 W
Weight (without terminal unit) Ca. 135 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40°C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.