Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process voltage | ||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP) | |
Rated value | 24 V DC | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP | 10 A fast | |
Galvanic isolation | Yes, per module | |
Current consumption | ||
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/bus module | Ca. 2 mA | |
Current consumption from UP in normal operation | 130 mA | |
Inrush current from UP (at power up) | On request | |
Max. length of analog cables, conductor cross section > 0.14 mm² | 100 m | |
Weight | 130 g | |
Mounting position | Horizontal or vertical with derating (max. temperature 40 °C) |
|
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Attention
:strong:Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.