Technical Data of the Analog Inputs

Parameter Value
Number of channels per module 8    
Distribution of channels into groups 2 groups of 4 channels each
Connections of the channels I0 to I3 Terminals 1.0 to 1.7 and terminals 2.0 to 2.7
Connections of the channels I4 to I7 Terminals 3.0 to 3.7 and terminals 4.0 to 4.7
Input type Bipolar (not with current or Pt100/Pt1000/Ni1000/Cu50/resistor)
Galvanic isolation Against internal supply and other modules
Configurability Digital input, -50 … +50 mV, -500 … +500 mV, -1 … +1 V, -5 … +5 V, -10 … +10 V, 0 … +5 V, 0 … +10 V, -20 … +20 mA, 0 … 20 mA, 4…20 mA, Pt100, Pt1000, Ni1000, Cu50, resistor, thermocouple types J, K, N, S, T (each input can be configured individually)
Channel input resistance Voltage: > 100 kΩ, current: ca. 330 Ω
Time constant of the input filter Line-frequency suppression 50 Hz, 60 Hz, none
Indication of the input signals 1 yellow LED per channel, the brightness depends on the value of the analog signal
Conversion time 1 ms (none), 100 ms (60 Hz), 120 ms (50 Hz) per channel
Resolution Range unipolar 15 bits
bipolar 15 bits + sign
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.1 % (voltage)

± 0.3 % (current, resistor)

at 25%

Max.

± 0.7 % (voltage)

± 0.9 % (current, resistor)

± 0.5 % (thermocouple)

1.0 K (resistance temperature detectors)

at 0…60 °C or EMC disturbance

Relationship between input signal and hex code Table Input Ranges AI531 - Analog Input Module
Unused voltage inputs Are configured as “unused”
Unused current inputs Have a low resistance, can be left open-circuited
Input data length 32 bytes
Overvoltage protection Yes