Technical Data of the Analog Inputs¶
Parameter | Value | ||
---|---|---|---|
Number of channels per module | 8 | ||
Distribution of channels into groups | 2 groups of 4 channels each | ||
Connections of the channels I0 to I3 | Terminals 1.0 to 1.7 and terminals 2.0 to 2.7 | ||
Connections of the channels I4 to I7 | Terminals 3.0 to 3.7 and terminals 4.0 to 4.7 | ||
Input type | Bipolar (not with current or Pt100/Pt1000/Ni1000/Cu50/resistor) | ||
Galvanic isolation | Against internal supply and other modules | ||
Configurability | Digital input, -50 … +50 mV, -500 … +500 mV, -1 … +1 V, -5 … +5 V, -10 … +10 V, 0 … +5 V, 0 … +10 V, -20 … +20 mA, 0 … 20 mA, 4…20 mA, Pt100, Pt1000, Ni1000, Cu50, resistor, thermocouple types J, K, N, S, T (each input can be configured individually) | ||
Channel input resistance | Voltage: > 100 kΩ, current: ca. 330 Ω | ||
Time constant of the input filter | Line-frequency suppression 50 Hz, 60 Hz, none | ||
Indication of the input signals | 1 yellow LED per channel, the brightness depends on the value of the analog signal | ||
Conversion time | 1 ms (none), 100 ms (60 Hz), 120 ms (50 Hz) per channel | ||
Resolution | Range | unipolar | 15 bits |
bipolar | 15 bits + sign | ||
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. | ± 0.1 % (voltage) ± 0.3 % (current, resistor) at 25% |
|
Max. | ± 0.7 % (voltage) ± 0.9 % (current, resistor) ± 0.5 % (thermocouple) 1.0 K (resistance temperature detectors) at 0…60 °C or EMC disturbance |
||
Relationship between input signal and hex code | Table Input Ranges AI531 - Analog Input Module | ||
Unused voltage inputs | Are configured as “unused” | ||
Unused current inputs | Have a low resistance, can be left open-circuited | ||
Input data length | 32 bytes | ||
Overvoltage protection | Yes |