Unipolar Voltage Input Range, \ Measuring Bridge, Digital Input

Range 0 … +5 V 0 … +10 V Digital input Digital value
        Decimal Hex.
Overflow > 5.8794 > 11.7589   32767 7FFF
Measured value too high

5.8794

:

5.0002

11.7589

:

10.0004

 

32511

:

27649

7EFF

:

6C01

Normal range

5.0000

:

0.0002

10.0000

:

0.0004

ON

27648

:

1

6C00

:

0001

0.0000 0.0000 OFF 0 0000
Measured value too low

-0.0002

:

-0.8794

-0.0004

:

-1.1759

 

-1

:

-4864

FFFF

:

ED00

Underflow < -0.8794 < -1.7589   -32768 8000