Parameterization

Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is performed by Control Builder Plus/ Automation_Builder software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Module: Module slot address: Y = 1…10

Name Value Internal value Internal value, Type Default Min. Max. EDS Slot/Index
Module ID Internal

1535

1)

Word

1535

0x05ff

0 65535 0x0Y01

Ignore module

2)

No

Yes

0

1

Byte

No

0x00

    Not for FBP
Parameter length in bytes Internal 36 Byte 36 0 255 0x0Y02
Check supply

Off

On

0

1

Byte

On

0x01

    0x0Y03
Analog data format Default 0 Byte

Default

0x00

    0x0Y04

1) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1

2) Not with FBP

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

39

0x05, 0xff, 0x24, \

0x01, 0x00, 0x00, 0x00 \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \

0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00;

Input channel (8x)

No. Name Value Internal value Internal value, Type Default EDS Slot Index
1 Channel configuration see AI531 - Analog Input Module see AI531 - Analog Input Module Byte

0

0x00

0x0Y07
2 Channel monitoring see AI531 - Analog Input Module see AI531 - Analog Input Module Byte

0

0x03

 
3 Line frequency suppression see AI531 - Analog Input Module see AI531 - Analog Input Module Byte

0

0x00

 
4 Compensation channel see AI531 - Analog Input Module see AI531 - Analog Input Module Byte

0

0x00

 
Channel Configuration
Internal value Operating modes for the analog inputs, individually configurable
0 Unused (default)
2 Digital input
34 Analog input -50 mV … +50 mV
35 Analog input -500 mV … +500 mV
36 Analog input -1 V … +1 V
7 Analog input -5 V … +5 V
5 Analog input -10 V … +10 V
6 Analog input 0 V … +5 V
1 Analog input 0 V … +10 V
37 Analog input -20 mA … +20 mA
3 Analog input 0 mA … 20 mA
4 Analog input 4 mA … 20 mA
14 Analog input Pt100 (2-wire), -50 °C … +70 °C
15 Analog input Pt100 (3-wire), -50 °C … +70 °C
48 Analog input Pt100 (4-wire), -50 °C … +70 °C
57 Analog input Pt100 (2-wire), -50 °C … +70 °C (resolution: 0,01 K)
58 Analog input Pt100 (3-wire), -50 °C … +70 °C (resolution: 0,01 K)
59 Analog input Pt100 (4-wire), -50 °C … +70 °C (resolution: 0,01 K)
8 Analog input Pt100 (2-wire), -50 °C … +400 °C
9 Analog input Pt100 (3-wire), -50 °C … +400 °C
49 Analog input Pt100 (4-wire), -50 °C … +400 °C
45 Analog input Pt100 (2-wire), -200 °C … +850 °C
46 Analog input Pt100 (3-wire), -200 °C … +850 °C
47 Analog input Pt100 (4-wire), -200 °C … +850 °C
16 Analog input Pt1000 (2-wire), -50 °C … +400 °C
17 Analog input Pt1000 (3-wire), -50 °C … +400 °C
50 Analog input Pt1000 (4-wire), -50 °C … +400 °C
18 Analog input Ni1000 (2-wire), -50 °C … +150 °C
19 Analog input Ni1000 (3-wire), -50 °C … +150 °C
51 Analog input Ni1000 (4-wire), -50 °C … +150 °C
39 Analog input Cu50 1.426 (2-wire) -50 °C … +200 °C
40 Analog input Cu50 1.426 (3-wire) -50 °C … +200 °C
41 Analog input Cu50 1.426 (4-wire) -50 °C … +200 °C
42 Analog input Cu50 1.428 (2-wire) -200 °C … +200 °C
43 Analog input Cu50 1.428 (3-wire) -200 °C … +200 °C
44 Analog input Cu50 1.428 (4-wire) -200 °C … +200 °C
24 Analog input J-type thermocouple -210 °C … +1200 °C
25 Analog input K-type thermocouple -270 °C … +1372 °C
30 Analog input N-type thermocouple -270 °C … +1300 °C
27 Analog input S-type thermocouple -50 °C … +1768 °C
28 Analog input T-type thermocouple -270 °C … +400 °C
38 Analog input resistor 50 kW
52 Temperature-internal reference point
53 Common mode voltage
Channel \ monitoring
Internal value Monitoring
0 Plausibility, open-circuit (cut wire) and short-circuit (default)
3 No monitoring
Line frequency suppression
Internal value Line frequency suppression
0 50 Hz
1 60 Hz
2 No line frequency suppression
Compensation channel
Internal value Compensation channel
0 Internal compensation (default)
1 Channel 0 (possible with channels 1, 2, 3)
2 Channel 1 (possible with channels 0, 2, 3)
3 Channel 2 (possible with channels 0, 1, 3)
4 Channel 3 (possible with channels 0, 1, 2)
5 Channel 4 (possible with channels 5, 6, 7)
6 Channel 5 (possible with channels 4, 6, 7)
7 Channel 6 (possible with channels 4, 5, 7)
8 Channel 7 (possible with channels 4, 5, 6)
9 External with temperature definition