Mounting and Demounting the Communication ModulesΒΆ

Communication Modules are mounted on the left side of the Processor Module on the same Terminal Base. The electrical connection is established automatically when mounting the Communication Module.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with β€”). Reserved terminals may carry internal voltages.

After mounting the Terminal Base, mount the Communication Modules.

  1. First insert the bottom nose of the Communication Module into the dedicated holes of the Terminal Base. Then, rotate the Communication Module on the dedicated Terminal Base slot until it is locked in place.

    β‡’
    ../_images/b6d6840ae9165f600a317f345a183924

    Attention

    :strong:Risk of malfunctions!

    Unused slots for communication modules are not protected against accidental physical contact.

    • Unused slots for communication modules must be covered with dummy communication modules (TA524 TA524 - Dummy Communication Module to achieve IP20 rating.
    • I/O bus connectors must not be touched during operation.
  2. The demounting is carried out in a reversed order.

    Press above and below, then rotate the Communication Module and remove it.

    β‡’
    ../_images/35c37ab0e91661820a317f345fc11b01