Operating Elements on the Front Panel

Status LEDs

Meaning of the status LEDs (left part)
LED Color Status Description
PWR *) Green On Power supply available
Blinking
Off Power supply not available or defective hardware
RDY *) Yellow On Boot procedure
Blinking Boot failure
Off
RUN *) Green On Communication module is operational
Blinking
Off Communication module is not operational
STA1 *) Red On Depending on used fieldbus
Blinking Depending on used fieldbus
Off Depending on used fieldbus
Green On Depending on used fieldbus
Blinking Depending on used fieldbus
Off Depending on used fieldbus
STA2 *) Red On Depending on used fieldbus
Blinking Depending on used fieldbus
Off Depending on used fieldbus
Green On Depending on used fieldbus
Blinking Depending on used fieldbus
Off Depending on used fieldbus

* These LEDs exist twice.

LED Color Status Description
PWR Green On Power supply available
Blinking
Off Power supply not available or defective hardware
RUN Green On Processor module is in RUN mode
Blinking
Off Processor module is in STOP mode
ERR Red/green On An error has occurred
Blinking Flashing fast (4 Hz): Indicates together with RUN a firmware update process and a flash EEPROM write.
Off No errors are encountered or only warnings (E4 errors). This is configurable (for errors 2 - 4, the LED behaviour is configurable.
- Red/green On Reserved
Blinking Reserved
Off Reserved
Batt Red/green On TA541 lithium battery is not installed or is weak
Blinking
Off TA541 lithium battery is installed and has sufficient capacity
1 Red/green On Reserved
Blinking Reserved
Off Reserved
2 Red/green On Reserved
Blinking Reserved
Off Reserved
3 Red/green On Reserved
Blinking Reserved
Off Reserved
4 Red/green On Reserved
Blinking Reserved
Off Reserved
5 Red/green On Reserved
Blinking Reserved
Off Reserved

Buttons and switches

The processor module can be operated manually using the buttons and switches at the front panel. Meaning of the buttons and switches:

Button Description
RESET If pressed during power-on: Enter serial download of firmware. This is signalized by blinking of the RUN LED with a frequency of 1 Hz. If pressed during normal operation: reserved for future implementation.
Fn If pressed during power-on: Bootproject will not be loaded. This is signalized by blinking of the RUN LED with a frequency of 1 Hz. If pressed during normal operation: reserved for future implementation.
RUN/STOP Switches the processor module from RUN to STOP mode.

The AC500 Processor Module can display various errors according to the error classes. The reaction of the Processor Module is different for each type of error. See System Technology LED display: LEDs, Display and Function Keys on the Front Panel