Technical Data of the Analog Inputs

Parameter Value
Number of channels per module 4 individually configurable voltage or current inputs
Distribution of channels into groups 1 (4 channels per group)
Resolution  
  Unipolar

Voltage: 0 V … +5 V; 0 V … + 10 V: 12 bits

Current 0 mA … 20 mA; 4 mA … 20 mA: 12 bits

  Bipolar Voltage -2.5 V … +2.5 V; -5 V … +5 V: 11 bits plus sign
Connection of the signals I0- to I3- Terminals 3, 6, 9, 12
Connection of the signals I0+ to I3+ Terminals 2, 5, 8, 11
Input type Differential
Galvanic isolation No galvanic isolation between the inputs and the I/O bus
Common mode input range Signal voltage plus common mode voltage must be within ± 12 V
Indication of the input signals No
Channel input resistance Voltage: >1 MW, current: ca. 250 W
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.5 % of full scale (voltage)

± 0.5 % of full scale (current 0…20 mA)

± 0.7 % of full scale (current 4…20 mA)

at 25°C

Max.

± 2 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Time constant of the input filter Voltage: 300 µs, current: 300 µs
Relationship between input signal and hex code Table Measuring Ranges AX561 - Analog Input/Output Module
Analog to digital conversion time Typ. 500 µs per channel
Unused inputs Can be left open and should be configured as “unused”
Input data length 8 bytes
Overvoltage protection Yes, up to 30 V DC only for voltage input
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m