Technical Data of the Analog Outputs

Parameter Value
Number of channels per module 2 configurable voltage or current outputs
Distribution of channels into groups 1 (2 channels per group)
Connection of the signals O0U- and O1U+ Terminals 13 and 15
Connection of the signals O0I+ and O1I+ Terminals 14 and 16
Output type Bipolar with voltage, unipolar with current
Resolution 12 bits or 11 bits plus sign
Indication of the output signals No
Output resistance (load) as current output 0 … 500 W
Output load ability as voltage output 2 mA max.
Relationship between input signal and hex code Table Output Ranges AX561 - Analog Input/Output Module
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

± 0.5 % of full scale (voltage)

± 0.5 % of full scale (current 0…20 mA)

± 0.7 % of full scale (current 4…20 mA)

at 25°C

Max.

± 2 % of full scale (all ranges)

at 0…60 °C or EMC disturbance

Unused outputs Can be left open and should be configured as “unused”
Output data length 4 bytes
Overvoltage protection Yes, up to 30 V DC
Max. cable length (conductor cross section > 0,14 mm²)  
  Unshielded wire 10 m
  Shielded wire 100 m