Parameters of the Module

Name Value Internal value Internal value, type Default
Module ID 1) Internal 0x1C89 WORD 0x1C89
Parameter length Internal 38 BYTE 38
Error LED / failsafe function table error LED / failsafe function CI582-CN) On 0 BYTE 0
Off by E4 1
Off by E3 2
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 18
Reserved 0 0 ARRAY of 24 BYTES  
Check supply On 0 BYTE  
Off 1 1
Fast counter 0 0 BYTE 0
: :  
10 2) 10  

1) With a faulty ID, the module reports a “parameter error” and does not perform cyclic process data transmission.

2) For a description of the counter operating modes, please refer to the Fast Counter section Fast Counter.

Error LED / Failsafe function
Setting Description
On Error LED (S-ERR) lights up at errors of all error classes, failsafe mode off
Off by E4 Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode off
Off by E3 Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode off
On + Failsafe Error LED (S-ERR) lights up at errors of all error classes, failsafe mode on *)
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode on *)
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode on *)
*) The parameter Behavior DO at comm. error is only analyzed if the failsafe mode is ON.