Parameters of the Module¶
| Name | Value | Internal value | Internal value, type | Default |
|---|---|---|---|---|
| Module ID 1) | Internal | 0x1C89 | WORD | 0x1C89 |
| Parameter length | Internal | 38 | BYTE | 38 |
| Error LED / failsafe function table error LED / failsafe function CI582-CN) | On | 0 | BYTE | 0 |
| Off by E4 | 1 | |||
| Off by E3 | 2 | |||
| On + failsafe | 16 | |||
| Off by E4 + failsafe | 17 | |||
| Off by E3 + failsafe | 18 | |||
| Reserved | 0 | 0 | ARRAY of 24 BYTES | |
| Check supply | On | 0 | BYTE | |
| Off | 1 | 1 | ||
| Fast counter | 0 | 0 | BYTE | 0 |
| : | : | |||
| 10 2) | 10 |
1) With a faulty ID, the module reports a “parameter error” and does not perform cyclic process data transmission.
2) For a description of the counter operating modes, please refer to the Fast Counter section Fast Counter.
| Setting | Description |
|---|---|
| On | Error LED (S-ERR) lights up at errors of all error classes, failsafe mode off |
| Off by E4 | Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode off |
| Off by E3 | Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode off |
| On + Failsafe | Error LED (S-ERR) lights up at errors of all error classes, failsafe mode on *) |
| Off by E4 + Failsafe | Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, failsafe mode on *) |
| Off by E3 + Failsafe | Error LED (S-ERR) lights up at errors of error classes E1 and E2, failsafe mode on *) |
| *) The parameter Behavior DO at comm. error is only analyzed if the failsafe mode is ON. | |