Group Parameters for the Digital Part

Name Value Internal value Internal value, type Default
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

0.1 ms

0x00

Detect short circuit at outputs

Off

On

0

1

BYTE

On

0x01

Behavior DO at comm. error 1)

Off

Last value

Last value 5 sec

Last value 10 sec

Substitute value

Substitute value 5 sec

Substitute value 10 sec

0

1

6

11

2

7

12

BYTE

Off

0x00

Substitute value at output 0 … 65535 0000h … FFFFh WORD

0

0x0000

Preventive voltage feedback monitoring for DC0..DC7 2)

Off

On

0

1

BYTE

Off

0x00

Detect voltage overflow at outputs 3)

Off

On

0

1

BYTE

Off

0x00

Remarks:

1) The parameter Behavior DO at comm. error is applied to DC and DO channels and only analyzed if the failsafe mode is ON.
2) The state “externally voltage detected” appears if the output of a channel DC0..DC7 is to be switched on while an external voltage is connected.  In this case, start-up is disabled while the externally voltage is connected. The monitoring of this state and the resulting diagnosis message can be disabled by setting the parameters to “OFF”.
3) The error state “voltage overflow at outputs” appears if external voltage at digital outputs DC0..DC7 and DO0..DO7 has exceeded the process supply voltage UP3 (see Electrical Connection CI582-CN). The according diagnosis message “Voltage overflow on outputs ” can be disabled by setting the parameters to “OFF”. This parameter should only be disabled in exceptional cases as voltage overflow may produce reverse voltage.