Electrical Connection

The function module CD522 can be connected to the following devices via the I/O bus connector:

  • FBP interface module DC505-FBP
  • CS31 bus module DC551-CS31
  • Processor module PM5xx
  • Other AC500 I/O devices.

The electrical connection is carried out by using the 40 terminals of the Terminal Unit TU515/TU516 TU515, TU516, TU516-H and TU542 for I/O Modules.

Assignment of the terminals
Terminal Signal Description
1.0 /A0 Inverted input signal A of encoder 0
1.1 /B0 Inverted input signal B of encoder 0
1.2 /Z0 Inverted input signal Z of encoder 0
1.3 5V0 +5 VDC power supply output 0 for sensors
1.4 0V 0 V reference input
1.5 O0 Output signal of the fast output O0
1.6 0V 0 V reference input
1.7 O1 Output signal of the fast output O1
1.8 UP Process voltage UP (24 VDC)
1.9 ZP Process voltage ZP (0 VDC)
2.0 A0 Input signal A of encoder 0
2.1 B0 Input signal B of encoder 0
2.2 Z0 Input signal Z of encoder 0
2.3 I3 Input signal I3 (standard input)
2.4…2.7 C4…C7 Signal of the configurable digital input/output C4…C7
2.8 UP Process voltage UP (24 VDC)
2.9 ZP Process voltage ZP (0 VDC)
3.0 /A1 Inverted input signal A of encoder 1
3.1 /B1 Inverted input signal B of encoder 1
3.2 /Z1 Inverted input signal Z of encoder 1
3.3 5V1 +5 VDC power supply output 1 for sensors
3.4…3.7 0V 0 V reference input
3.8 UP Process voltage UP (24 VDC)
3.9 ZP Process voltage ZP (0 VDC)
4.0 A1 Input signal A of encoder 1
4.1 B1 Input signal B of encoder 1
4.2 Z1 Input signal Z of encoder 1
4.3 I11 Input signal I11 (standard input)
4.4…4.7 C12…C15 Signal of the configurable digital input/output C12…C15
4.8 UP Process voltage UP (24 VDC)
4.9 ZP Process voltage ZP (0 VDC)

The internal power supply voltage for the module’s circuitry is carried out via the I/O bus (provided by a bus module or a processor module). Thus, the current consumption from 24 VDC power supply at the terminals L+/UP and M/ZP of the processor/bus module increases by 2 mA per CD522.

The external power supply connection is carried out via the UP (+24 VDC) and the ZP (0 VDC) terminals.

Warning

:strong:Removal/Insertion under power

The devices are not designed for removal or insertion under power. Because of unforeseeable consequences, it is not allowed to plug or unplug devices with the power being ON.

Make sure that all voltage sources (supply and process voltage) are switched off before you

  • connect or disconnect any signal or terminal block
  • remove, mount or replace a module.

Disconnecting any powered devices while energized in a hazardous location could result in an electric arc, which could create a flammable ignition resulting in fire or explosion.

Make sure that power is removed and that the area has been thoroughly checked to ensure that flammable materials are not present prior to proceeding.

The devices must not be opened when in operation. The same applies to the network interfaces.

Attention

:strong:Risk of damaging the PLC modules!

Overvoltages and short circuits might damage the PLC modules.

  • Make sure that all voltage sources (supply and process voltage) are switched off before you begin with operations at the system.
  • Never connect any voltages or signals to reserved terminals (marked with —). Reserved terminals may carry internal voltages.

Connection of Encoders with Differential RS-422 Signal

The encoder is powered by the 5 V power supply which is integrated in CD522.

../_images/8e903f7f94c901540a33139031765fc7

Connection of Encoders with 5 V TTL Signal

The encoder is powered by the 5 V power supply which is integrated in the CD522.

../_images/1a58835494ca2e5c0a3313902cbc9b7a

Connection of Encoders with 24 V Totem Pole Signal

../_images/b038d7f394cafdbb0a33139066be62b8

Note

The wires A, B and Z need not to be connected to the module. They are left open.

Note

When using different power supplies for the encoder device and the CD522, make sure that the reference potentials of both power supplies are interconnected.

Connection of Encoders with 1 Vpp Sine Signal

The encoder is powered through the 5 V power supply which is integrated in the CD522.

../_images/9a8251f394cbf0b10a331390419e2825

Connection of Absolute Encoders with SSI Interface and Differential \ RS-422 Signal

The encoder is powered by the 5 V power supply which is integrated in the CD522.

../_images/a7ef7abde388ce8b0a33139000eba54e

Connection of Absolute Encoders with an SSI Interface and an \ Optocoupler Interface at CLK Input

The encoder can optionally be powered by the 5 V power supply which is integrated in the CD522.

../_images/df37482494cecfaa0a3313901b3e1494

Connection of Output Loads to the PWM/Pulse Putputs

../_images/00cf8c8a94cfac710a33139070c8027f

Attention

:strong:Risk of damaging the Module

The PWM outputs have no protection against reverse polarity.

Connection of Standard Inputs/Outputs

Proceed with the inputs/outputs I11 and C12-C15 in the same way.

../_images/1b8c25f494d0b8050a3313901c01ef37

Connection of Sensors with Frequency Outputs

Proceed with the A0, B0, A1, B1 and Z1 in the same way.

../_images/0115f55394d1a7520a331390662402eb

Example of the electrical connection of sensors with frequency outputs to the input Z0 of the CD522

Attention

:strong:Risk of malfunctions!

The edges of a signal must be strong enough (0.4 V/µs) to be recognized correctly by the module.

Put a 1 kW resistor between 0 V and the Z terminal when using a standard output as time generator.

Connection of Sensors to the 5 V Power Supply

Proceed with the 5 V power supply 1 in the same way.

Note

Each 5-V-power supply provides a current of 100 mA max. It is possible to parallel both integrated power supplies. In this case, the max. current is 200 mA.

../_images/aedc38b894d2c4e10a3313904267b836

Attention

:strong:Risk of Damaging the Module

The integrated 2A fuse cannot be replaced. If it blows, the module must be replaced.

Ensure that the current per 0 V connection does not exceed 0.5 A.

Attention

:strong:Risk of Damaging the Module

The two 5 V outputs have no protection against reverse polarity.