TU515, TU516, TU516-H and TU542 for I/O Modules¶
- TU515, I/O terminal unit, 24 VDC, screw terminals
- TU516, I/O terminal unit, 24 VDC, spring terminals
- TU516-H, I/O terminal unit, hot swap, 24 VDC, spring terminals
- TU542, I/O terminal unit, hot swap, 24 VDC, spring terminals
- XC version for use in extreme ambient conditions available (TU516 and TU542 only)
Hot Swap
H = Hot swap
Note
:strong:Hot swap
- Hot-swappable terminal units have the appendix TU5xx:strong:-H.
- I/O modules as of index F0.
- Communication interface modules CI5xx as of index F0.
Note
The index of the module is in the right corner of the label.
Attention
:strong:Risk of damage to I/O modules!
Modules with index below F0 can be damaged when inserted or removed from the terminal unit in a powered system.
Note
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed or inserted during operation.
Attention
:strong:Risk of damage to I/O modules!
Do not perform any hot swap action if any I/O module with firmware version lower than 3.0.14 (for index see table below) is contained in the affected cluster.
Device | Min. required device index for I/O module FW Version as of 3.0.14 |
---|---|
DO573, FM562, DI572 |
A1 |
DO526 DC562 DO562 |
A2 |
DO526 (-XC) | A0 |
CD522 (-XC) | D1 |
DO524 (-XC) | A3 |
AI531 | D4 |
DA501 (-XC), DI524 (-XC), DC532 (-XC), DC523 (-XC), DC522 (-XC), AX521 (-XC), AO523 (-XC), AI523 (-XC), AX522 (-XC), AI531-XC, DX531, DX522 (-XC), |
D2 |
AI561, AI562, AO561, AX561, DC561, DI561, DI562, DI571, DO561, DO572, DX561 |
B2 |
AI563, DO571, DX571 |
B3 |
XC Version
XC = eXtreme Conditions
Note
:strong:Extreme conditions
Terminal units for use in extreme ambient conditions have no sign for XC version.
The figure 4 in the Order No. 1SAP4… (lable) identifies the XC version.
The input/output modules (decentralized communication interface modules) plug into the I/O terminal unit. When properly seated, they are secured with two mechanical locks. All the electrical connections are established via the terminal unit, which allows removal and replacement of the I/O modules without disturbing the wiring at the terminal unit.
The I/O terminal units TU515, TU516, TU516-H and TU542 are specifically designed for use with AC500/S500 I/O modules that incorporate only 24 VDC or analog inputs/outputs.
Screw terminals | Spring terminals | ||||
---|---|---|---|---|---|
Conductor | Screwdriver | Conductor | Screwdriver (opens terminal) |
Note
For a detailed description of the mounting, disassembly and electrical connection of the terminal units and the I/O modules, please refer to the “System Assembly, Construction and Connection” chapter AC500 (Standard).
The following terminals are used for connection of the process voltage supply.
Terminals | ||||||||
---|---|---|---|---|---|---|---|---|
Type | 1.8 | 2.8 | 3.8 | 4.8 | 1.9 | 2.9 | 3.9 | 4.9 |
TU515, TU516 and TU516-H | These terminals are internally connected with assignment: process voltage UP = +24 VDC | These terminals are internally connected with assignment: process voltage ZP = 0 V | ||||||
TU542 | These terminals are internally connected with assignment: process voltage UP = +24 VDC | Separate process voltage UP3 = +24 VDC | Separate process voltage UP4 = +24 VDC | These terminals are internally connected with assignment: process voltage ZP = 0 V | Separate process voltage ZP = 0 V | Separate process voltage ZP = 0 V |
The assignment of the other terminals depends on the inserted decentralized communication interface module (see the description of the respective module used).