Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply to the analog inputs¶
The following figure shows the connection of active-type analog sensors (voltage) with no electrically isolated power supply to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Caution
:strong:Risk of faulty measurements!
The minus pole at the sensors must not have a too big potential difference with respect to ZP (max. ± 1 V).
Make sure that the potential difference never exceeds ± 1 V (also not with long cable lengths).
The following measuring ranges can be configured CI501-PNIO CI501-PNIO:
Voltage | 0…10 V | 1 channel used |
Voltage | -10 V…+10 V | 1 channel used |
The function of the LEDs is described under Diagnosis and displays / Displays CI501-PNIO.
To avoid error messages from unused analog input channels, configure them as “unused”.