Connection of active-type analog sensors (current) with electrically \ isolated power supply to the analog inputs

The following figure shows the connection of active-type analog sensors (current) with electrically isolated power supply to the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.

../_images/37b1e6b6e38884df0a33139000eba54e

The following measuring ranges can be configured CI501-PNIO CI501-PNIO:

Current 0…20 mA 1 channel used
Current 4…20 mA 1 channel used

The function of the LEDs is described under Diagnosis and displays / Displays CI501-PNIO.

Unused input channels can be left open-circuited, because they are of low resistance.

To avoid error messages through unused analog input channels in measuring range 4…20 mA, these channels should be configured as “Not used”.