The state of the ETHERNET communication module is displayed by means of 5 state LEDs. The following figure shows the positions of the LEDs. The table after that shows the LED states and their meanings.

../_images/1d9981b773ccc89c0a317f3457a969f5
LED Color Status Description
PWR Green On Power supply available
Off Power supply not available or defective hardware
RDY Yellow On Boot procedure
Blinking Boot failure
RUN Green On Communication module is operational
Off Communication module is not operational
STA1 Green Blinking (1 Hz) Device ready
Blinking (5 Hz) Device configured / UDP traffic
On MODBUS communication established
STA2 Red On MODBUS communication error
Off No error
STA1 and STA2

Red

Green

Blinking (synchronously) Firmware file transfers during coupler firmware update

Red

Green

Blinking (alternately) Coupler writes the firmware file to the internal flash. Do not power off the PLC.

Yellow

Yellow

Blinking (synchronously) No production data available, no bus communication possible.

The RJ45 ETHERNET connector contains two LEDs showing the current ETHERNET port connection state. The following figure and table show the position and function of the LEDs:

../_images/92d6bebce387c1240a33139000eba54e
LED Color Status Description
ETH1 LED “Link” Green On ETHERNET connection established
Off No ETHERNET connection
ETH1 LED “RX/TX” Yellow On
Blinking Device sends/receives frames
Off
ETH2 LED “Link” Green On ETHERNET connection established
Off No ETHERNET connection
ETH2 LED “RX/TX” Yellow On
Blinking Device sends/receives frames
Off