Diagnosis¶
In case of overload or short-circuit, the outputs switch off automatically and try to switch on again cyclically. Therefore an acknowledgement of the outputs is not necessary. The LED error message, however, is stored.
E1..E4 | d1 | d2 | d3 | d4 | Identifier 000..063 |
AC500 display | <− Display in | |
---|---|---|---|---|---|---|---|---|
Class | Comp | Dev | Mod | Ch | Err | PS501 PLC browser | ||
Byte 6 Bit 6..7 |
- | Byte 3 | Byte 4 | Byte 5 | Byte 6 Bit 0..5 |
FBP diagnosis block | ||
Class | Interface | Device | Module | Channel | Error identifier | Error message | Remedy | |
1) | 2) | 3) | 4) | |||||
Module error | ||||||||
3 | 11 | ADR | 31 | 31 | 19 | Checksum error in the I/O module | Replace I/O module | |
3 | 11 | ADR | 31 | 31 | 3 | Timeout in the I/O module | ||
3 | 11 | ADR | 31 | 31 | 40 | Different hard-/firmware versions in the module | ||
3 | 11 | ADR | 31 | 31 | 43 | Internal error in the module | ||
3 | 11 | ADR | 31 | 31 | 36 | Internal data exchange failure | ||
3 | 11 | ADR | 31 | 31 | 9 | Overflow diagnosis buffer | New start | |
3 | 11 | ADR | 31 | 31 | 26 | Parameter error | Check master | |
3 | 11 | ADR | 31 | 31 | 11 | Process voltage too low | Check process voltage | |
3 | 11 | ADR | 1…7 | 31 | 17 | No communication to the I/O module | Replace I/O module | |
4 | 11 | ADR | 31 | 31 | 45 | Process voltage ON/OFF | Process voltage ON | |
4 | 11 | ADR | 31/1..7 | 31 | 34 | No reply at initialization of the I/O module | Replace I/O module | |
4 | 11 | ADR | 31/1.7 | 31 | 32 | Wrong I/O module in the slot | Replace I/O module or check configuration | |
Channel error DC551-CS31 | ||||||||
4 | 11 | ADR | 31/1..7 | 8..23 | 47 | Short-circuit at a digital output | Check connection |
Remarks:
1) | In AC500 the following interface identifier applies: 11 = COM1 (protocol CS31 bus only possible with COM1) |
2) | With “Device” and CS31 bus master, the hardware address of the DC551-CS31 (0…69) is output. |
3) | With “Module” the following allocation applies: 31 = Module itself, 1…7 = Expansion 1…7 |
4) | In case of module errors, with channel “31 = Module itself” is output. |