Electromagnetic Compatibility¶
Immunity | ||
---|---|---|
Immunity against electrostatic discharge (ESD): | According to EN 61000-4-2, zone B, criterion B | |
Electrostatic voltage in case of air discharge | 8 kV | |
Electrostatic voltage in case of contact discharge | 4 kV, in a closed switch-gear cabinet 6 kV 1) | |
ESD with communication connectors | In order to prevent operating malfunctions, it is recommended, that the operating personnel discharge themselves prior to touching communication connectors or perform other suitable measures to reduce effects of electrostatic discharges. | |
ESD with connectors of Terminal Bases | The connectors between the Terminal Bases and Processor Modules or Communication Modules must not be touched during operation. The same is valid for the I/O-Bus with all modules involved. | |
Immunity against the influence of radiated (CW radiated): | According to EN 61000-4-3, zone B, criterion A | |
Test field strength | 10 V/m | |
Immunity against transient interference voltages (burst): | According to EN 61000-4-4, zone B, criterion B | |
Supply voltage units (AC, DC) | 4 kV | |
Digital inputs/outputs (24 V DC) | 2 kV | |
Digital inputs/outputs (120/230 V AC) | 2 kV | |
Analog inputs/outputs | 1 kV | |
CS31 system bus | 2 kV | |
Serial RS-485 interfaces (COM) | 2 kV | |
Serial RS-232 interfaces (COM, not for PM55x and PM56x) | 1 kV | |
ARCNET | 1 kV | |
FBP | 1 kV | |
Ethernet | 1 kV | |
I/O supply, DC-out | 1 kV | |
Immunity against the influence of line-conducted interferences (CW conducted): | According to EN 61000-4-6, zone B, criterion A | |
Test voltage | 3V zone B, 10 V is also met. | |
High energy surges | According to EN 61000-4-5, zone B, criterion B | |
Power supply DC | 1 kV CM / 0.5 kV DM ²) | |
DC I/O supply | 0.5 kV CM / 0.5 kV DM ²) | |
Communication Lines, shielded | 1 kV CM ²) | |
AC-I/O unshielded | 2 kV CM / 1 kV DM ²) | |
I/O analog, I/O DC unshielded | 1 kV CM / 0.5 kV DM ²) | |
Radiation (radio disturbance) | According to EN 55011, group 1, class A |
1) High requirement for shipping classes are achieved with additional specific measures (see specific documentation).
²) CM = Common Mode, DM = Differential Mode