State LEDs

During the power ON procedure, the module initializes automatically. All LEDs (except the channel LEDs) are ON during this time.

LED State Color LED = OFF LED = ON LED flashes
Outputs 0…7 Digital output yellow Output = OFF Output = ON 2)
UP Process supply voltage 24 VDC via terminal green Process supply voltage is missing Process supply voltage OK
UP3 Process supply voltage outputs 0 … 3 24 VDC via terminal green Process supply voltage is missing Process supply voltage OK
UP4 Process supply voltage outputs 4 … 7 24 VDC via terminal green Process supply voltage is missing Process supply voltage OK
CH-ERR3 Channel Error, error messages in groups (digital outputs combined into the groups 3, 4) red No error or process supply voltage is missing Severe error within the corresponding group Error on in the corresponding group
CH-ERR4 red
CH-ERR 1) Module Error red Internal error

1) All of the LEDs CH-ERR3 to CH-ERR4 light up together

2) The state of the LEDs corresponds to the logic state of the output. In case of missing or low process supply voltage UP3 or UP4, the signal on the output terminal is off even though the LED is on.