Group parameters for the digital part

Name Value Internal value Internal value, type Default
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

0.1 ms

0x00

Detect short circuit at outputs

Off

On

0

1

BYTE

On

0x01

Behaviour DO at comm. error 1)

Off

Last value

Last value 5 sec

Last value 10 sec

Substitute value

Substitute value 5 sec

Substitute value 10 sec

0

1

6

11

2

7

12

BYTE

Off

0x00

Substitute value at output 0 … 65535 0000h … FFFFh WORD

0

0x0000

Preventive voltage feedback monitoring for DC0..DC7 2)

Off

On

0

1

BYTE

Off

0x00

Detect voltage overflow at outputs 3)

Off

On

0

1

BYTE

Off

0x00

Remarks:

1) The parameter Behaviour DO at comm. error is apply to DC and DO channels and only analyzed if the Failsafe-mode is ON.
2) The status “externally voltage detected” appears, if the output of a channel DC0..DC7 should be switched on while an externally voltage is connected.  In this case the start up is disabled, as long as the externally voltage is connected. The monitoring of this state and the resulting diagnosis message can be disabled by setting the parameters to “OFF”.
3) The error status “voltage overflow at outputs” appears, if externally voltage at digital outputs DC0..DC7 and accordingly DO0..DO7 has exceeded the process supply voltage UP3 CI542-DP. The according diagnosis message “Voltage overflow on outputs ” can be disabled by setting the parameters on “OFF”. This parameter should only be disabled in exceptional cases for voltage overflow may produce reverse voltage.