Parameters of the Module

Name Value Internal value Internal value, type Default
Module ID *1) Internal 0x1C25 WORD 0x1C25
Parameter length Internal 31 BYTE 31
Reserved (1 byte) 0 0 BYTE 0
Error LED / Failsafe function CI542-DP (see table ) On 0 BYTE 0
Off by E4 1
Off by E3 2
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 18
Reserved (20 bytes) 0 0 BYTE 0
Check supply On 0 BYTE  
Off 1 1
Fast counter 0 0 BYTE 0
: :  
10 *2) 10  

*1) With a faulty ID, the module reports a “parameter error” and does not perform cyclic process data transmission.

*2) Counter operating modes, see Fast Counter Fast Counter.

ErrorLED / Failsafe function
Setting Description
On Error-LED (S-ERR) lights up at errors of all error classes, Failsafe mode off
Off by E4 Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe mode off
Off by E3 Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe mode off
On + Failsafe Error-LED (S-ERR) lights up at errors of all error classes, Failsafe mode on*
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3, Failsafe mode on*
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1 and E2, Failsafe mode on*
*) The parameter Behaviour DO at comm. error is only analyzed if the Failsafe mode is ON.