Technical Data¶
The System Data of AC500-eCo apply System Data AC500-eCo
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Process supply voltage L+ | ||
Connections | Terminal 20 for L+ (+24 V DC). The negative pole is provided by the I/O bus. | |
Rated value | 24 V DC | |
Current consumption via L+ | 50 mA | |
Inrush current (at power-up) | 0.0035 A²s | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Rated protection fuse for UP | Recommended; the outputs must be protected by a 3 A fast fuse | |
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module | Ca. 5 mA | |
Galvanic isolation | Yes, between the output group and the rest of the module | |
Isolated groups | 2 (4 channels per group) | |
Surge-voltage (max.) | 35 V DC for 0.5 s | |
Max. power dissipation within the module | 2.0 W | |
Weight | Ca. 150 g | |
Mounting position | Horizontal or vertical | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.