Technical Data

The System Data of AC500-eCo apply System Data AC500-eCo

Only additional details are therefore documented below.

Parameter Value
Process supply voltage L+  
  Connections Terminal 20 for L+ (+24 V DC). The negative pole is provided by the I/O bus.
  Rated value 24 V DC
  Current consumption via L+ 50 mA
  Inrush current (at power-up) 0.0035 A²s
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse for UP Recommended; the outputs must be protected by a 3 A fast fuse
Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module Ca. 5 mA
Galvanic isolation Yes, between the output group and the rest of the module
Isolated groups 2 (4 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 2.0 W
Weight Ca. 150 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.