Connection of active-type analog sensors (voltage) with no electrically \ isolated power supply

../_images/5a74d8e9e3880f530a331390015ea5a7

Connection example

Caution

The potential difference between AGND and ZP at the module must not be greater than 1V, not even in case of long lines (see figure Terminal Assignment).

Note

If AGND does not get connected to ZP, the sensor current flows to ZP via the AGND line. The measuring signal is distorted, as a very small current flows through the voltage line. The total current through the PTC should not exceed 50 mA. This measuring method is therefore only suitable for short lines and small sensor currents. If there are bigger distances, the difference measuring method should be applied.

Voltage 0…10 V 1 channel used
Voltage -10 V…+10 V *) 1 channel used

*) if the sensor can provide this signal range

In order to avoid error messages or long processing times, it is useful to configure unused analog input channels as “unused”.