Connection of passive-type analog sensors (current)

../_images/928cdc1fe3880fb00a331390015ea5a7

Connection example

Current 4…20 mA 1 channel used

Caution

If, during initialization, an analog current sensor supplies more than 25 mA for more than 1 second to an analog input, this input is switched off by the module (input protection). In such cases, it is recommended to protect the analog input by a 10-volt Zener diode (in parallel to I+ and I-). But, in general, sensors with fast initialization or without current peaks higher than 25 mA are preferrable.

Unused input channels can be left open-circuited because they are of low resistance.