Channel \ Parameters for the Analog Outputs (2x)¶
Name | Value | Internal value | Internal value, type | Default |
---|---|---|---|---|
Output 0, Channel configuration | see table 3) | see table 3) | BYTE | 0 |
Output 0, Check channel | see table 4) | see table 4) | BYTE | 0 |
Output 0, Substitute value | see table 5) | see table 5) | WORD | 0 |
Output 1, Channel configuration | see table 3) | see table 3) | BYTE | 0 |
Output 1, Check channel | see table 4) | see table 4) | BYTE | 0 |
Output 1, Substitute value | see table 5) | see table 5) | WORD | 0 |
Internal value | Operating modes of the analog outputs, individually configurable |
---|---|
0 (default) | Not used |
128 | -10 V…+10 V |
129 | 0…20 mA |
130 | 4…20 mA |
Internal value | Check channel |
---|---|
0 | Plausib(ility), cut wire, short circuit |
3 | None |
Intended behaviour of output channel when the control system stops | Required setting of the module parameter “Behaviour of outputs in case of a communication error” | Required setting of the channel parameter “Substitute value” |
---|---|---|
Output OFF | Off | 0 |
Last value infinite | Last value | 0 |
Last value for 5 s and then turn off | Last value 5 sec | 0 |
Last value for 10 s and then turn off | Last value 10 sec | 0 |
Substitute value infinite | Substitute value | Depending on configuration |
Substitute value for 5 s and then turn off | Substitute value 5 sec | Depending on configuration |
Substitute value for 10 s and then turn off | Substitute value 10 sec | Depending on configuration |