Group Parameters for the Digital Part¶
Name | Value | Internal value | Internal value, type | Default |
---|---|---|---|---|
Input delay | 0.1 ms 1 ms 8 ms 32 ms |
0 1 2 3 |
BYTE | 0.1 ms 0x00 |
Fast counter | No counter 1 Up counter 1 Up counter with release input 2 UpDown counters 2 UpDown (2. On falling edges) 1 Updown dynamic set/rising edge 1 Updown dynamic set/falling edge 1 UpDown directional discriminator Reserved 1 UpDown directional discriminator x2 1 UpDown directional discriminator x4 |
0 1 2 3 4 5 6 7 8 9 10 |
BYTE | 0 |
Detect short circuit at outputs | Off On |
0 1 |
BYTE | On 0x01 |
Behaviour DO at comm. error *) | Off Last value Last value 5 sec Last value 10 sec Substitute value Substitute value 5 sec Substitute value 10 sec |
0 1 6 11 2 7 12 |
BYTE | Off 0x00 |
Substitute value at output | 0…255 | 00h…FFh | BYTE | 0 0x0000 |
*) The parameters Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.