Parameters of the Module - if used without Fast Counter¶
| Name | Value | Internal value | Internal value, type | Default |
|---|---|---|---|---|
Module ID 1) |
Internal | 2726 | WORD | 2726 |
| Parameter length | Internal | 23 | BYTE | 23 |
Error LED / Failsafe function 2) |
On | 0 | BYTE | 0 |
| Off by E4 | 1 | |||
| Off by E3 | 3 | |||
| On + failsafe | 16 | |||
| Off by E4 + failsafe | 17 | |||
| Off by E3 + failsafe | 19 | |||
| Check supply | Off | 0 | BYTE | |
| On | 1 | 1 |
Remarks:
1) With a faulty Module ID, the Modules reports a “parameter error” and does not perform cyclic process data transmission
2) Error LED/Failsafe function:
| Setting | Description |
|---|---|
| On | Error-LED lights up at errors of all error classes, Failsafe mode off |
| Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode off |
| Off by E3 | Error LED lights up at errors of error classes E1 and E2, Failsafe mode off |
| On +Failsafe | Error-LED lights up at errors of all error classes, Failsafe mode on *) |
| Off by E4 + Failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafe mode on *) |
| Off by E3 + Failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafe mode on *) |
*) The parameters behaviourAOatCommunicationFault and behaviourDOatCommunicationFault are only analyzed if the Failsafe mode is ON.