Parameters of the Module - if used with Fast Counter

Name Value Internal value Internal value, type Default
Module ID 1) Internal 2725 WORD 2725
Parameter length Internal 22 BYTE 22
Error LED / Failsafe function 2) On 0 BYTE 0
Off by E4 1
Off by E3 3
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 19
Check supply off 0 BYTE  
on 1 1

Note

If the bus module is configured as a Fast Counter module and ‘0 - no Counter’ in Automation_Builder is selected the channel ERR LEDs stays on and the module does not start up. The address was adjusted with ‘71’.

Only the ‘0- no Counter’ mode does not operate. If any other counter is selected e.g. ‘1-1 Up counter’ the module starts up and can be utilized.