Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Parameter Value
Process supply voltage UP  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
  Rated value 24 V DC
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
  Galvanic isolation Yes, per module
Current consumption  
  From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/bus module ca. 2 mA
  From UP at normal operation / with outputs 0.15 A + output loads
Inrush current from UP (at power up) 0.004 A:sup:2s
Max. power dissipation within the module 6 W (outputs OFF)
Weight (without terminal unit) Ca. 300 g
Mounting position Horizontal or vertical with derating (output load reduced to 50 % at 40°C per group)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Attention

:strong:Attention:

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 VDC.

No effects of multiple overloads

No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.