Technical Data of the Relay OutputsΒΆ
Parameter | Value | |
---|---|---|
Number of channels per module | 4 relay outputs | |
Distribution of channels into groups | 4 groups of 1 channel each | |
Connection of the four relays | See figure Electrical Connection DX531 - Digital Input/Output Module | |
Galvanic isolation | Between the channels and from the rest of the module | |
Indication of the output signals | 1 yellow LED per channel, the LED is ON when the relay coil is energized | |
Way of operation | Non-latching type | |
Output delay (0->1 or 1->0) | On request | |
Output data length | 1 byte | |
Relay power supply | By UP process voltage | |
Relay outputs | ||
Output short-circuit protection | Must be provided externally with a fuse or circuit breaker | |
Rated protection fuse | 6 A gL/gG per channel | |
Output switching capacity | ||
Resistive load, max. | 3 A; 3 A (230 V AC), 2 A (24 V DC) | |
Inductive load, max. | 1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC) | |
Lamp load | 60 W (230 V AC), 10 W (24 V DC) | |
Life time (cycles) | Mechanical: 300 000; Under load: 300 000 (24 V DC at 2 A), 200 000 (120 V AC at 2 A), 100 000 (230 V AC at 3 A) |
|
Spark suppression with inductive AC load | Must be performed externally according to driven load specifications | |
Demagnetization with inductive DC load | A free-wheeling diode must be circuited in parallel to the inductive load | |
Switching frequency | ||
With resistive load | Max. 10 Hz | |
With inductive load | Max. 2 Hz | |
With lamp load | On request | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |