Technical Data¶
The System Data of AC500-eCo apply System Data AC500-eCo
Only additional details are therefore documented below.
| Parameter | Value | |
|---|---|---|
| Process supply voltage UP | ||
| Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) | |
| Rated value | 24 V DC | |
| Current consumption via UP terminal | 5 mA + max. 0.5 A per output | |
| Max. ripple | 5 % | |
| Inrush current | 0.000002 A²s | |
| Protection against reversed voltage | Yes | |
| Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse | |
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/bus module | Ca. 10 mA | |
| Galvanic isolation | Yes, between the input group and the output group and the rest of the module | |
| Isolated groups | 2 groups (1 group for 8 input channels, 1 group for 8 output channels) | |
| Surge-voltage (max.) | 35 V DC for 0.5 s | |
| Max. power dissipation within the module | 2.3 W | |
| Weight | ca. 120 g | |
| Mounting position | Horizontal or vertical | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |
No effects of multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is protected individually by an external fuse.