Technical Data of the Digital Outputs

Parameter Value
Number of channels per module 8 transistor outputs (24 V DC, 0.5 A max.)
Distribution of the channels into groups 1 group of 8 channels
Connection of the channels O0 to O7 Terminals 11 to 18
Reference potential for the channels O0 to O7 Terminal 20 (negative pole of the process voltage, name ZP)
Common power supply voltage Terminal 19 (positive pole of the process voltage, name UP)
Indication of the output signals 1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered via the I/O bus
Way of operation Non-latching type
Max. output voltage at signal 1 20 V DC at max. current consumption
Output delay  
  0 to 1 50 µs
  1 to 0 200 µs
Output data length 1 byte
Output current  
  Rated current per channel (max.) 0.5 A at UP 24 V DC
  Rated current per group (max.) 4 A
  Rated current (all channels together, max.) 4 A
  Lamp load (max.) 5 W
  Max. leakage current with signal 0 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 3 A fast
Demagnetization when inductive loads are switched off Must be performed externally according to driven load specification
Switching Frequencies  
  With inductive loads Max. 0.5 Hz
  With lamp loads Max. 11 Hz at max. 5 W
Short circuit / Overload proof No
  Overload message No
  Output current limitation No
  Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Max. cable length  
  Shielded 500 m
  Unshielded 150 m